Warning will occur. The default values for these set-
points are 203° F and a delay of 5 seconds.
High Motor Temp Warning - Shaft Side – The mo-
tor has temperature sensors that monitor the Shaft
Side bearing. If the temperature of this bearing ex-
ceeds the Shaft Side High Warning setpoint, for a pe-
riod of time exceeding the Shaft Side High Warning
Delay setpoint, this Warning will occur. The default
values for these setpoints are 203° F and a delay of
5 seconds.
High Motor Vib Shutdown - Opposite Shaft Side
- If the Opposite Shaft Side Drive Vibration sensor
registers a reading that is higher than the value that
has been set for the Opposite Shaft High Shutdown,
for the period of time as set for the Opposite Shaft
High Shutdown Delay, a Shutdown will be generated.
The default values for these setpoints are 10 Fg and
a delay of 1 second.
High Motor Vib Shutdown - Shaft Side - If the
Shaft Side Drive Vibration sensor registers a reading
that is higher than the value that has been set for the
Shaft Side High Shutdown, for the period of time as
set for the Shaft Side High Shutdown Delay, a Shut-
down will be generated. The default values for these
setpoints are 10 Fg and a delay of 1 second.
High Motor Vib Warning - Opposite Shaft Side - If
the Opposite Shaft Side Drive Vibration sensor reg-
isters a reading that is higher than the value that has
been set for the Opposite Shaft High Warning, for
the period of time as set for the Opposite Shaft High
Warning Delay, a warning will be generated. The de-
fault values for these setpoints are 3.5 Fg and a delay
of 99 seconds.
High Motor Vib Warning - Shaft Side - If the Shaft
Side Drive Vibration sensor registers a reading that is
higher than the value that has been set for the Shaft
Side High Warning, for the period of time as set for
the Shaft Side High Warning Delay, a warning will be
generated. The default values for these setpoints are
3.5 Fg and a delay of 99 seconds.
High Oil Filter Pressure Shutdown - The Oil Filter
Pressure was greater than or equal to the High Fil-
ter Pressure Shutdown setpoint for its time delay.
The default values for these setpoints are 30 PSI and
a delay of 10 minutes. If the Filter setting is "Filter
minus Oil", use the absolute value of the fi lter dif-
ferential when checking the High Oil Filter Pressure
safeties.
High Oil Filter Pressure Warning - The Oil Filter
Pressure was greater than or equal to the High Filter
Pressure Warning setpoint for its time delay. The de-
fault values for these setpoints are 25 PSI and a delay
of 15 minutes. If the Filter setting is "Filter minus Oil",
use the absolute value of the fi lter differential when
checking the High Oil Filter Pressure safeties.
QUANTUM™ LX COMPRESSOR CONTROL PANEL
OPERATION
High Oil Pressure (Kobe) – If the compressor type is
set to Other Manufacturer (Kobe), the oil pump type
is set to Demand and if Oil Pressure rises above 325
PSIA for more than 5 seconds this shutdown will oc-
cur. This shutdown is only active when the compres-
sor is running and is also not checked for the fi rst 90
seconds after the compressor starts.
High Oil Separator Temp Sensor Warning – This
warning message is issued if the Oil Separator Tem-
perature reading (analog board 1, channel 4) was to
the upper or maximum range (out of range) for its
sensor.
High Oil Temperature Sensor Fault – This shutdown
message is issued if the Oil Temperature reading (an-
alog board 1, channel 3) was to the upper or maxi-
mum range (out of range) for its sensor.
High Oil Temp Compressor Sensor Warning – This
warning message is issued if the Oil Temperature
reading (analog board 1, channel 3) was to the upper
or maximum range (out of range) for its sensor.
High Process Entering Temp Sensor Warning – This
warning message is issued if the Process Entering
Temperature reading (analog board 2, channel 4) was
to the upper or maximum range (out of range) for its
sensor.
High Process Entering Temp Shutdown - The Enter-
ing Process Temperature was greater than or equal
to the High Entering Process Temperature Shutdown
setpoint for its time delay.
High Process Entering Temp Warning - The Enter-
ing Process Temperature was greater than or equal
to the High Entering Process Temperature Warning
setpoint for its time delay.
High Process Leaving Temp Sensor Warning – This
warning message is issued if the Process Leaving
Temperature reading (analog board 1, channel 5) was
to the upper or maximum range (out of range) for its
sensor.
High Process Leaving Temp Shutdown - The Leav-
ing Process Temperature was greater than or equal
to the High Leaving Process Temperature Shutdown
setpoint for its time delay.
High Process Leaving Temp Warning - The Leaving
Process Temperature was greater than or equal to
the High Leaving Process Temperature Warning set-
point for its time delay.
High Rem Capacity Position Sensor Warning – This
warning message is issued if the Remote Capacity
Position reading was to the upper or maximum range
(out of range) for its sensor.
High Remote Control Setpoint Sensor Warning –