Ac Power Flowchart - Simplex 4010 Service Manual

Hide thumbs Also See for 4010:
Table of Contents

Advertisement

AC Power Flowchart

Technical Manuals Online! - http://www.tech-man.com
NO
Meter AC Power
@ Panel's AC
Terminal Block.
AC Power Less
than 103 VAC?
YES
NO
Brownout Adjustment
Potentiometer Correctly
Positioned? Refer to
Appendix B.
YES
NO
Meter DC Power
@ Terminals H1 and H2
DC Power 21-32 VDC?
Contact Individual / Organization
Responsible for Building Electrical
System
Adjust Brownout Potentiometer.
Note: Read Appendix B for
Adjustment Procedure.
Check and Replace (if necessary)
Transformer and Bridge Rectifier.
Refer to Appendix B.