4.1.2.2 Function Description
Function
Function Name
Code
Refrigerant
A2
recycle
Cooling/heating of
A6
the entire system
Outdoor silence
A7
mode
After-sales
A8
vacuum pumping
mode
Auto energy
n0
saving
n3
Forced defrosting
Forced energy
n4
saving
Indoor unit
n5
engineering SN
offset
One-button
drainage of
qJ
dual-heat-source
units
Compressor
emergency
C8
setting
Module
emergency
CA
setting
Fan emergency
C9
setting
Outdoor static
1G
pressure setting
Description
This function is automatically
started during maintenance. Based
on the system pressure change,
this function recycles all or partial
refrigerant of the faulty module or
the indoor unit pipeline.
The unit can be set to cooling and
heating, cooling only, heating only,
or fan mode for centralized
management.
This function sets different silence
modes based on the user's needs.
During maintenance, the system
automatically turns on all electronic
expansion valves and solenoid
valves to ensure that all lines can
be vacuumed.
This function can automatically
reduce power consumption of the
unit based on system operating
parameters.
This function forcibly enables
defrosting of the outdoor unit of the
system.
This function forcibly reduces the
maximum power consumption of
the unit.
When different refrigerating
systems are controlled in a
centralized manner, this function
avoids the conflict of indoor unit
engineering numbers.
This function opens the water
valves of all dual-heat-source
indoor units in the system.
—
—
—
—
47
GMV6 HR DC Inverter VRF Units Service Manual
Default Setting
Code
Meaning
—
Cooling and
nA
heating
00
No silence
—
Capability
01
priority
control
—
100%
10
capability
output
—
—
Normal
operation of
00
compressor
Normal
00
operation of
the module
Normal
00
operation of
the fan
0 Pa static
00
pressure
Remarks
This function can
—
only be set.
This function can
be set and
queried.
This function can
be set and
queried.
This function can
—
only be set.
This function can
be set and
queried.
This function can
—
only be set.
This function can
be set and
queried.
This function can
—
only be set.
This function is
applicable to
—
drainage in
non-heating
seasons.
—
the
—
—
—