Gree
Step 6: Discharging refrigerant
The refrigerant in the system needs to be discharged from the high and low pressure sides of
the system concurrently. If the refrigerant is discharged from one side only, the sealed scroll will
hinder the refrigerant from being fully discharged. Do not discharge the refrigerant too fast (in no
shorter than 12h). Otherwise, a large amount of lubricant will be discharged together with the
refrigerant as well.
Step 7: Removing compressors
(1)Remove the fixing nut, gasket and damping washer of compressor.
(2)Weld the welding point for nozzle
A. Applicable model: GMV-VQ224/280/335/400/450WM/C-X
GMV6 HR DC Inverter VRF Units Service Manual
1—nut
2—gasket
336
3—damping washer