2.56 "d7" Humidity Sensor Fault
Fault display: wired controller of indoor unit and receiver of indoor unit display
Fault diagnosis:
The temperature sensor detection circuit samples the AD value of temperature sensor and
determines the range of AD value. When the sampled AD value exceeds the limits for 5 consecutive
seconds, the fault is generated.
Possible causes:
■ Poor contact between the humidity sensor and the main board interface;
■ Abnormal humidity sensor;
■ Abnormal detection circuit.
Troubleshooting:
"d6" Outlet P ipe
Temperature Sen sor Fault
Whether th e i nter face
contains forei gn matters?
No
Is th e p roblem so lve d after
is re placed?
No
The detection circuit may
ope rate impro perly
GMV6 HR DC Inverter VRF Units Service Manual
Yes
matters and plug it tightly
Yes
Replace th e main control
boa rd