Gree
(4) If the measured resistance does not match with that in the following table, the coil needs to
be replaced.
Coil
Main cooling 4-way
valve
Heating 4-way valve
GMV6 HR DC Inverter VRF Units Service Manual
Resistance (Ω)
Interface No.
CN23
CN21
251
Normal range of deviation
2085
2085
±10%
±10%