Siemens SIRIUS 3RK3 Equipment Manual page 352

Modular safety system
Hide thumbs Also See for SIRIUS 3RK3:
Table of Contents

Advertisement

Diagnostics / service
7.10 Replacement of AS-i components
If the newly inserted, safety-related AS-i slave already has the correct address, it is enough to
close the contacts on the safety-related AS-i slave in order for the MSS 3RK3 to be able to receive
the new code sequence.
If the new safety-related AS-i slave has to be included on the bus by the AS-i master, it is first
necessary to wait for the autoadressing phase of the AS-i master. During the autoaddressing
phase, the new AS-i slave is addressed through address "0." This is not monitored by the MSS
3RK3. The system does not detect the new AS-i slave until it is provided with a correct address.
Teaching the new code sequences
If a safety-related AS-i slave is replaced, the MSS 3RK3 detects that the code sequence
transmitted by the AS-i slave is not contained in the code sequence table. This initially results in
the substitute value "0" being used in the interconnection logic for this slave.
Note
Important requirement
Before the code sequences are taught, both contacts of the safety-related AS-i input slaves must
be closed to enable the code sequences to be taught.
If the contacts are not closed, calculation in the logic diagram continues with the substitute
value "0." The current status of the AS-i slave is displayed in the "Learn ASIsafe code tables" dialog
box in Safety ES.
If MSS 3RK3 has ascertained after a monitoring period has elapsed that the new code sequence
is unique, the TEACH-LEDs will indicate that the new code sequence can be used instead of the
originally used code sequence. The new code sequence is applied and saved if you press the
RESET button for 3 s or use the "Apply learned AS-i code tables" command.
Table 7-1
LED
DEVICE
AS-i
TEACH
SF
Table 7-2
LED
DEVICE
AS-i
TEACH
SF
You will find further information in Chapter "Teaching the code sequences (Page 208)".
352
LED display during teaching of code sequences
Display
green
flickering green
flashing red
yellow flashing
Off
LED display if the code tables can be applied
Display
green
flickering green
flashing red
yellow
Off
Explanation
Device in safety mode
Device in test mode
Other code sequence on the AS-i bus
Teaching of code sequences active: The code sequences
are being taught.
No group error
Explanation
Device in safety mode
Device in test mode
Other code sequence on the AS-i bus
Code sequences can be applied
No group error
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006

Advertisement

Table of Contents
loading

This manual is also suitable for:

3rk3 basicSirius 3rk3 advancedSirius 3rk3 asisafe basicSirius 3rk3 asisafe extended

Table of Contents