Diagnostics / service
7.3 Diagnostics with LEDs
7.3.2.7
Displays on expansion module 2/4F-DI 2F-DO
LED
SF / IN1
IN2, IN3,
IN4,
Q1, Q2
7.3.2.8
Displays on expansion module 4F-DO
LED
SF / Q1
Q2, Q3,
Q4,
266
Display
Explanation
off
Input signal not present
green
Input signal present
green flashing
Error detected (cross-circuit at input / wirebreak / short-circuit to power
(1.75 s
cable / discrepancy error / feedback circuit error / sequence error / error
on / 0.25 s off)
during startup test)
Input signal present
green flashing
Error detected (cross-circuit at input / wirebreak / short-circuit to power
(0.75 s
cable / discrepancy error / feedback circuit error / sequence error / error
on / 1.25 s off)
during startup test)
Input signal not present
red
Device defective or error on the system bus
(see also Chapter ""SF" on the expansion module lights up red
(Page 256)")
off
Input signal not present
green
Input signal present
green flashing
Error detected (cross-circuit at input / wirebreak / short-circuit to power
(1.75 s
cable / discrepancy error / feedback circuit error / sequence error / error
on / 0.25 s off)
during startup test)
Input signal present
green flashing
Error detected (cross-circuit at input / wirebreak / short-circuit to power
(0.75 s
cable / discrepancy error / feedback circuit error / sequence error / error
on / 1.25 s off)
during startup test)
Input signal not present
off
Output signal not present
green
Output signal present
Display
Explanation
off
Output signal not present
green
Output signal present
red
Device defective or error on the system bus
(see also Chapter ""SF" on the expansion module lights up red
(Page 256)")
Off
Output signal not present
Green
Output signal present
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006