Setting the device name with SIRIUS Safety ES
Options and procedures
The SIRIUS Safety ES parameterization software provides various options for setting the device
name:
• Setting in the "Properties interface module" dialog
The device name can be set in the "Properties interface module" in "Configuration".
Thus, the device name is a part of the configuration that is loaded into the safety relay. This
option is always given.
It is always possible to change the device name in the "Properties interface module" dialog.
• When setting the communication interface (PROFINET service in SIRIUS Safety ES)
The device name can be set during the setting of the communication interface, e.g. via the
menu command "Target system" > "Edit Ethernet node...".
As a result, the device name is saved in the IO device and the IO device can be reached via
PROFINET. The configuration can then be transferred via the PROFINET interface.
The requirement for changing the device name when setting the communication interface
is the setting of the parameter "Ethernet addresses - Change authorizations" to "Can be
changed without restrictions". The setting of the change authorizations can be
parameterized in the "Properties interface module" dialog.
Result
The device communicates with the assigned name and the IP parameters assigned by the IO
controller.
Setting the device name via the automation system
Requirements
The requirement for changing the device name via the automation system (e.g. STEP 7) is the
setting of the parameter "Ethernet addresses - Change authorizations" to "Can be changed
without restrictions". The setting of the change authorizations can be changed in the SIRIUS
Safety ES in the "Properties interface module" dialog.
The device name is transferred to the IO device via Ethernet during the commissioning phase by
the configuration tool of the automation system. For transmission, the PROFINET interface must
be connected and accessible via the Ethernet interface. Using the MAC address (e.g.
00‑0E‑8C‑BD‑1F‑27) printed on the front of the PROFINET interface, the device can be accessible
via LAN. The device name is linked with the MAC address and thus represents the MAC address.
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006
6.6 Integration into PROFINET master systems