Bus errors
The following bus errors can be diagnosed:
Message
DP bus error
DP parameterization error
DP configuration error
ASi bus error
ASi parameterization error
ASi configuration error
SC bus error
SC parameterization error
SC configuration error
3RK3 Advanced and 3RK3 ASIsafe only
1)
2)
3RK3 only
Group warning
The following group warnings can be diagnosed:
Message
Disconnect
Group warning from user pro‐
gram
Configuration missing
Pressing the right key (OK) switches the diagnostics display directly to the element in the status menu.
1)
Group prewarning
The following group prewarnings can be diagnosed:
Message
User program stopped.
Group prewarning from user
program
Pressing the right key (OK) switches the diagnostics display directly to the element in the status menu.
1)
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006
1)
1)
1)
2)
2)
2)
1)
1)
Meaning
Communication via the fieldbus interface is interrupted.
An error occurred during parameterization for an existing communica‐
tion connection.
The actual configuration of an existing communication connection
does not match the target configuration. This resulted in an error.
Communication via the AS‑i interface is interrupted.
An error occurred during parameterization for an existing communica‐
tion connection.
1)
The actual configuration of an existing communication connection
does not match the target configuration. This resulted in an error.
Communication via the system interface is interrupted.
An error occurred during parameter assignment for an existing com‐
munication connection.
2)
The actual configuration of an existing communication connection
does not match the target configuration. This resulted in an error.
Meaning
The monitoring time has been exceeded During monitoring time, the
safety relay has not received any data set from the communication
partner with write access to the safety relay.
At least one warning from the user program is present.
No valid configuration is stored in the safety relay.
Meaning
The safety relay is not processing the safety circuit.
At least 1 configured function element has a group prewarning.
Diagnostics / service