Operation
6.4 Integrating into DP master systems
Key functions
The menu option DP•• is used to change the PROFIBUS address. You start input of the hundreds
digit by pressing "SET".
The buttons have the following functions when entering the address:
Pushbutton
"SET"
"MODE"
Double-click on "SET"
Double-click on "MODE" •
"MODE" and "SET" simul‐
taneously
Example: Setting the hundreds digit
Display
DP••
••*26
Result
Display
•XXX
OK•••
200
Result
•
Accepting the setting
•
Moving to the next digit:
Hundreds, tens, units digit
•
Acceptance of the DP address following input of the units digit
•
Setting the flashing digit of the DP address
•
Counts up
•
Jumps back one place to the previous digit:
Units, tens, hundreds digit
Sets the flashing digit of the DP address
•
Counts down
•
The operation is canceled.
"EXIT" must then be confirmed by pressing "SET".
1st line: not flashing
2nd line: 1st digit in DP address
flashing
1st line: not flashing
2nd line: flashing
Action
The 2nd line in the display contains the current DP
address (0 ... 126; right-justified). If an address has
not yet been set, the default address 126 is dis‐
played.
•
By pressing "MODE", the hundreds are incre‐
mented (sequence: 0, 1, 0, etc.)
•
When you choose "SET", this digit is confirmed
and the system switches to the tens.
•
By double-clicking on "SET", you can go back
one digit (i.e. from the hundreds to the units).
The address is not applied when you do this.
Meaning
The message above indicates that the PROFIBUS
address was successfully saved. You can acknowl‐
edge this message by choosing "SET" or "MODE".
The display then returns to standard mode.
The set PROFIBUS address is applied immediately
on the bus side. You do not need to switch the
power OFF / ON.
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006