Byte posi‐
Message
tion
8
Start condition not ful‐
1
filled
8
... 8
Reserved=0
2
7
EMERGENCY STOP messages
The following table shows the messages with the associated byte arrangement in the element
data block of the "EMERGENCY STOP" function element.
Byte posi‐
Message
tion
0
0
Startup test required
0
1
Reserved=0
0
Discrepancy condition
2
violated
0
3
Safety sensor triggered
0
... 0
Reserved=0
4
7
1
0
Cross-circuit at input 1
1
... 1
Reserved=0
1
3
1
Cross-circuit at input 2
4
1
... 1
Reserved=0
5
7
2
Start signal duration in‐
0
valid
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006
Meaning
is set if:
•
A sensor test was not executed in the
case of an active startup test function
•
A discrepancy condition violation is
present
•
The value "1" is not present simultane‐
ously at all available (parameterized)
function inputs (IN1, ...)
•
A signal sequence violation is present
•
A cross-circuit is present in the case of
cross-circuit monitoring
Meaning
This message is set in a parameterized startup
test on each restart and each time the substitute
value is changed to a real value until the con‐
nected sensor is actuated at least once.
is set if:
•
After the discrepancy time has elapsed, the
signal states at the inputs monitored are dif‐
ferent
•
The signal states of the inputs monitored
had not all previously been reset simultane‐
ously to the value "0" when they are set to "1"
The safety sensor has been actuated.
A cross-circuit was detected at input 1.
A cross-circuit was detected at input 2.
Only with start type "Monitored start":
The start signal time monitoring element detec‐
ted a violation.
7.6 Diagnosis using AS-Interface (CTT2 protocol)
Element status
‑
Element status Cyclic data
SVW
Logic error
SVW
Wiring error
Wiring error
‑
Diagnostics / service
Cyclic data
‑
SVW
SF
SVW
SF
SF
‑