Siemens SIRIUS 3RK3 Equipment Manual page 254

Modular safety system
Hide thumbs Also See for SIRIUS 3RK3:
Table of Contents

Advertisement

Diagnostics / service
7.3 Diagnostics with LEDs
LED response
SF-LED on cen‐
Input LEDs on central
tral unit
unit or expansion mod‐
ule
flashing red
The IN LEDs of a sensor
are flashing green.
--
Basic: The IN LEDs of a
sensor are flashing
green.
Advanced/ASIsafe: The
sensor that triggered the
sequence violation is
flashing green.
One or more IN LEDs
flashing green.
The error was detected at
this input.
254
Sensor connected to responding IN
inputs
Monitoring Universal
EMERGENCY STOP
ESPE
Protective door
Safety shutdown mat with NC prin‐
ciple
Two-hand operation
Enabling button
Protective door with lock
Muting functions
Muting functions
Monitoring Universal
Protective door
Protective door with lock
Muting functions
Meaning/Causes
Discrepancy condition violated
For further information, see Safety ES
Discrepancy condition violated
Other meanings for Advanced/
ASIsafe:
Pushbutton stuck
Do not release both pushbuttons
For further information, see Safety ES
Discrepancy condition violated
Other meanings for Advanced/
ASIsafe:
Pushbutton stuck
For further information, see Safety ES
Discrepancy condition violated
Interlock not possible because the
protective door is open
Discrepancy condition sensor pair x
not fulfilled
Max. muting time exceeded
Sequence condition not fulfilled
The sequence condition was not
fulfilled in accordance with the pa‐
rameter assignment.
Sequence condition not fulfilled
(muting)
The sequence condition was not
fulfilled in accordance with the pa‐
rameter assignment.
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006