Diagnostics / service
7.6 Diagnosis using AS-Interface (CTT2 protocol)
Messages for safety shutdown mat (cross-circuit principle)
The following table shows the messages with the associated byte arrangement in the element
data block of the "safety shutdown mat with cross-circuit principle" function element.
Byte posi‐
Message
tion
6
Startup test required
0
6
... 6
Reserved=0
1
2
6
Safety sensor triggered
3
6
... 6
Reserved=0
4
7
7
Wire break at input 1
0
7
Short circuit to P at input 1
1
7
2
... 7
3
Reserved=0
7
Wire break at input 2
4
7
Short circuit to P at input 2
5
7
... 7
Reserved=0
6
7
8
Start signal duration invalid
0
8
1
Start condition not fulfilled
8
... 8
Reserved=0
2
7
320
Meaning
This message is set in a parameter‐
ized startup test on each restart and
each time the substitute value is
changed to a real value until the
connected sensor is actuated at
least once.
The safety sensor has been actu‐
ated.
A cross-circuit was detected at input
1.
A short-circuit to P was detected at
input 1.
A cross-circuit was detected at input
2.
A short-circuit to P was detected at
input 2.
Only with start type "Monitored
start":
The start signal time monitoring el‐
ement detected a violation.
is set if:
A sensor test was not executed
in the case of an active startup
test function
The value "1" is not present si‐
multaneously at all available
(parameterized) function in‐
puts (IN1, ...)
A cross-circuit is present
Element status
SVW
SVW
Wiring error
Wiring error
Wiring error
Wiring error