Channel-related diagnostics
Channel-related diagnostics contains the error number from DS92. Up to six errors can be
transferred simultaneously. The MSS 3RK3 uses the following error numbers:
Note
Difference between the 3RK3 central units
The error numbers of the 3RK3 central units are not all identical.
Error
Description
no.
7
Upper limit exceeded
8
Lower limit undershot
9
Error
16
Parameterization error
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006
Byte
Length
12 bytes
0 ... 18 bytes
DP error numbers
Explanation
Memory module too small
Max. number of elements exceeded
Max. size of memory exceeded
Program cycle time exceeded
Device error
Self-test error
Configuring error:
Release denied due to incorrect configura‐
tion CRC
Release canceled due to incorrect configura‐
tion release CRC
Invalid parameter value
Interconnection rule violated
(not in the case of MSS 3RK3 Basic)
Data structure incorrect
(not in the case of MSS 3RK3 Basic)
7.5 Diagnostics using PROFIBUS
Diagnostics block
Status messages
Device-related diagnostics
Channel-related diagnostics
(max. 6 channels of 3 bytes each) Error numbers
Remedy
Reduce configuring
Adapt configuring
Replace device
Correct configuring
Update engineering software
Diagnostics / service
291