11.6

MODULE SETTING

No.
Items
Module
1.
Power On Mode
2.
Module Address
3.
Language
4.
Password
5.
Start Mode
Power Supply Rated
6.
Voltage
Power Supply Over
7.
Voltage Warn
Power Supply Under
8.
Voltage Warn
Extension Module
9.
DIN16-1 Enabled
10.
Alarm Delay
Extension Module
11.
DIN16-2 Enabled
12.
Alarm Delay
Extension Module
13.
DOUT16-1Enabled
14.
Alarm Delay
Extension Module
15.
DOUT16-2Enabled
16.
Alarm Delay
LED Display
17.
Extension Module 1
Enabled
18.
Alarm Delay
LED Display
19.
Extension Module 2
Enabled
20.
Alarm Delay
21.
GOV Transducer
HMC6 Power Management Controller User Manual
Table 24– Module Parameter Settings
Parameter Range
(0-2)
(1-254)
(0-2)
(0-65535)
(0-2)
(10.0-50.0)V
(50-200)%
(1-100)%
(0-1)
0: Disable
1: Enable
(0.1~999.9)s
(0-1)
0: Disable
1: Enable
(0.1~999.9)s
(0-1)
0: Disable
1: Enable
(0.1~999.9)s
(0-1)
0: Disable
1: Enable
(0.1~999.9)s
(0-1)
0: Disable
1: Enable
(0.1~999.9)s
(0-1)
0: Disable
1: Enable
(0.1~999.9)s
Transducer
Default
0: Semi Auto Mode; 1: Auto Mode;
0
2: Manual Mode.
1
Controller's address during remote sensing.
0
0: Simplified Chinese 1: English 2: Other.
00318
For entering advanced parameters setting.
0: Linear start; 1: Cycle start; 2: Duty Time
0
Start
To offer standards for detecting of power's
24.0
over/under voltage.
To offer standards for detecting of
130
percentage of power's over voltage.
To offer standards for detecting of
80
percentage of power's under voltage.
0: Disable
Connect with extension module DIN16-1
5.0
when input ports of HMC6 are not enough; If
still not enough, the external DIN16-2 is
extended.
0: Disable
5.0
0: Disable
Connect with extension module DOUT16-1
5.0
when input ports of HMC6 are not enough; If
still not enough, the external DOUT16-2 is
0: Disable
extended.
5.0
0: Disable
2 Connect with extension module LA16-1
5.0
when LED lamps of HMC6 are not enough; If
still not enough, the external LA16-2 is
0: Disable
extended.
5.0
0
One of GOV analog voltage regulating output
Description