Slot#1 Power Supply And Relay Output Port; Slot#2, Slot #3 Relay Output Port - Smartgen HMC6 User Manual

Power management controller
Table of Contents

Advertisement

Terminal description:NO means normally open; NC means normally close.
9.2.1
SLOT #1 POWER SUPPLY AND RELAY OUTPUT PORT
Terminal
1
B-
2
B+
3
AUX.OUTPUT1
4
AUX.OUTPUT2
5
AUX.OUTPUT3
6
COM1
NOTE: In case of using battery as power source, make the controller connect to the battery directly instead of start battery
or charging generator to ensure stable supply of HMC6.
9.2.2
SLOT #2, SLOT #3 RELAY OUTPUT PORT
Terminal
7
RAISE SPEED
8
COM2
9
DROP SPEED
10
AUX. OUTPUT 7
11
COM3
12
AUX. OUTPUT 8
13
ENGINE START
14
COM4
15
ENGINE STOP
16
GB CLOSE_NC
17
GB CLOSE _COM
18
GB CLOSE _NO
19
GB OPEN _NC
20
GB OPEN _COM
21
GB OPEN _NO
22
AUX. OUTPUT 9
23
HMC6 Power Management Controller User Manual
Table 11 – Slot#1 Power Supply & Relay Output Port
Function
Table 12 – Slot#2, Slot#3 Relay Output Port
Function
Description
DC(8~35)V
Auxiliary output port 1
Auxiliary output port 2
Auxiliary output port 3
COM port 3~5
Description
Raise speed output
COM port 7,9
Drop speed output
Default: Raise volt output
COM port 10,12
Default: Drop volt output
Engine start
COM port 13, 15
Engine stop
GB CLOSE output
GB OPEN output
Default: Audible alarm output
Remarks
Power supply input
AC250V/8 A
AC250V/8 A
AC250V/8 A
Remarks
AC250V/8 A
AC250V/8 A
AC250V/8 A
AC250V/8 A
AC250V/8 A
AC250V/8 A
AC250V/8 A
AC250V/8 A
AC250V/8 A
Page 28 of 87