9.3.3
AC WIRE CONNECTION (SINGLE PHASE 2 WIRE)
9.3.4
AC WIRE CONNECTION (2 PHASE 3 WIRE)
9.3.5
ANALOG INPUT
HMC6 FREQ IN and VOLT IN ports support -10V~10V analog voltage input function. External power supply
must be fitted when input signal.
Function
External frequency adjust
FREQ IN+
External active power adjust
External voltage adjust
VOLT IN+
External reactive power adjust
HMC6 Power Management Controller User Manual
Fig.6 – Single Phase 2 Wire Connection
Fig.7 – 2 Phase 3 Wire Connection
Table 18 - FREQ IN and VOLT IN Function Description
Description
External Setpoint Trigger Bar
Single unit running or generator breaker
is opened.
HMC6
is
paralleled
power/shaft generator/busbar and need
consistent power output.
Single unit running or generator breaker
is opened.
HMC6
is
paralleled
power/shaft generator/busbar and need
consistent power output.
Input Voltage
+/-10V DC
with
shore
+/-10V DC
+/-10V DC
with
shore
+/-10V DC
Page 32 of 87