Smartgen HMC6 User Manual page 48

Power management controller
Table of Contents

Advertisement

No.
Items
Set
43
44
45
46
Under
Frequency 2
47
Set
48
49
50
Under
Frequency 3
51
Set
52
53
54
ROCOF Set
55
56
57
58
VECTOR SHIFT
59
60
61
HMC6 Power Management Controller User Manual
Parameter Range
1: Enable
Set value
(80-100)%
Delay
(0.1-100.0)s
Alarm Type (0-5)
(0-1)
Action
0: Disable
1: Enable
Set value
(80-100)%
Delay
(0.1-100.0)s
Alarm Type (0-5)
(0-1)
Action
0: Disable
1: Enable
Set value
(80-100)%
Delay
(0.1-100.0)s
Alarm Type (0-5)
(0-1)
Action
0: Disable
1: Enable
Set value
(0-1.00)Hz/s
Delay
(0-20.0)s
Alarm Type (0-5)
(0-1)
Action
0: Disable
1: Enable
Set value
(0-20.0)°
Delay
(0-20.0)s
Alarm Type (0-5)
Default
96
5.0
1:Warn
1:Enable
93
10.0
2:Trip
0:Disable
92
8.0
2:Trip
0:Disable
When the controller detects that the
busbar ROCOF has exceeded the set
0.20
value, it will initiate an alarm signal and
the alarm information will be displayed
on LCD.
0.1
1:Warn
0:Disable
When the controller detects that the
busbar VECTOR SHIFT has exceeded
6.0
the set value, it will initiate a alarm
signal and the alarm information will be
displayed on LCD.
0.1
1:Warn
Description