Generator Setting - Smartgen HMC6 User Manual

Power management controller
Table of Contents

Advertisement

No.
Items
Operate Stop Delay
12
Cooling Delay
13
HC Stable Delay
14
HC ACK Delay
15
11.3

GENERATOR SETTING

No.
Items
Generator
1
AC System
2
Rated Voltage
3
Loading Voltage
4
Crank Success Volt
5
Rated Frequency
6
Loading Frequency
7
Crank Success Frequency
HMC6 Power Management Controller User Manual
Parameter Range
(0-3600)s
(0-3600)s
(0-1000)s
(0-1000)s
Table 21 – Generator Parameter Settings
Parameter Range
(0-3)
0: 3P4W
(30-30000)V
230
(0-200)%
95
(0-200)%
30
(10.0-75.0)Hz
50.0
(0-200)%
85
(0-200)%
65
Default
Stop delay caused by human triggered
1
(e.g. manual transfer priority, high
consumer request and etc.)
High speed cooling time before stop
0
output.
After busbar retardant power meet with
5
high consumer request, high consumer
ACK output after this delay.
After busbar retardant power meet with
5
high consumer request, high consumer
ACK output after "HC Stable Delay".
Default
0: 3 phase, 4 wire (3P4W);
1: 3 phase, 3 wire (3P3W);
2: 2 phase, 3 wire (2P3W);
3: 1 phase, 2 wire (1P2W).
To offer standards for detecting of
generator's over/under voltage. (It is
primary voltage when using voltage
transformer; it is line voltage when AC
system is 3P3W while it is phase
voltage when using other AC system).
Setting
generator rated voltage. Detect when
controller
generator voltage under load voltage,
won't enter into normally running.
To offer standards for detecting crank
disconnect voltage is satisfied or not.
To offer standards for detecting of
over/under/load frequency.
Setting
generator
when controller prepare loading. When
generator
frequency, it won't enter into normal
running.
To offer standards for detecting crank
Description
Description
value
is
percentage
prepare
loading.
value
is
percentage
rated
frequency.
frequency
under
Page 50 of 87