Smartgen HMC6 User Manual page 59

Power management controller
Table of Contents

Advertisement

No.
Items
Configuration
AVR Transducer
22.
Configuration
23.
HMP300 Enable
24.
Self-check
25.
Abnormal Return to
Manual
Engine Failure
26.
Action
27.
Controller Type
28.
SG Working Mode
Restart During
29.
Shutdown
30.
T54 Is Ready
HMC6 Power Management Controller User Manual
Parameter Range
Configuration (0-20)
Output Minimum
Output Maximum
Configure Minimum
Configure
Maximum
Transducer
Configuration (0-20)
Output Minimum
Output Maximum
Configure Minimum
Configure
Maximum
(0-1)
(0.1~999.9)s
(0-1)
(0-5)
(0-1)
(0-2)
(0-1)
0:Disable
1:Enable
(0-1)
0:Disable
1:Enable
Default
2.0
and transducer output can only be chosen.
10
0
500
0
2.0
One of AVR analog voltage regulating output
10
and transducer output can only be chosen.
0
500
0: Disable
5.0
Alarm delay.
It forces the controller into manual mode if
0: Disable
the self-check is abnormal.
Types of effective alarm action for engine
0: Lock
fault input port.
0: DG mode
0
1: SG mode
0: Load receiving mode
0
1: Fixed power mode
2: Load sharing mode
0: Disable
When it is enabled, it can restart the unit.
When it is enabled, the function of Terminal
0: Disable
54 will change from ' Engine Fault Input' to
'Unit is Ready Input'.
Description