Smartgen HMC6 User Manual page 67

Power management controller
Table of Contents

Advertisement

No.
Items
19
Contents Setting
20
Active Type
Programmable Output 2
21
Contents Setting
22
Active Type
Programmable Output 3
23
Contents Setting
24
Active Type
Programmable Output 4
25
Contents Setting
26
Active Type
Programmable Output 5
27
Contents Setting
28
Active Type
Programmable Output 6
29
Contents Setting
30
Active Type
No.
0.
Not Used
1.
Speed Raise
2.
Speed Drop
3.
Volt Raise
4.
Volt Drop
5.
Close Gen
6.
Open Gen
7.
Generator OK
8.
Common Alarm
9.
Common Warning
10.
Common Trip
11.
Common Shutdown
12.
Engine Start
13.
Engine Stop
14.
Power Over Volt
15.
Power Under Volt
HMC6 Power Management Controller User Manual
Parameter Range
(0-150)
(0-1)
(0-150)
(0-1)
(0-150)
(0-1)
(0-150)
(0-1)
(0-150)
(0-1)
(0-150)
(0-1)
Table 29 – Output Ports Function
Name
This port is invalid.
Active when the generator is raising speed.
Active when the generator is dropping speed.
Active when the generator is raising voltage.
Active when the generator is dropping voltage.
Active when the close generator requirements are
reached.
Active when the open generator requirements are
reached.
Active when the rated voltage and rated frequency are
reached.
Active when genset common alarm occurs.
Active when genset common warning alarm occurs.
Active when genset common trips alarm occurs.
Active when genset common trip and stop alarm
occurs.
Active when genset is starting up.
Active when genset is stopping.
Active when the power supply voltage has exceeded
the set value.
Active when the power supply voltage has fallen below
the set value.
Default
0
Not Used
0
0: Open 1: Close。
0
Not Used
0
0: Open 1: Close
0
Not Used
0
0: Open 1: Close
0
Not Used
0
0: Open 1: Close
0
Not Used
0
0: Open 1: Close
0
Not Used
0
0: Open 1: Close
Description
Description
Remark
Page 67 of 87