3.5 POWER MANAGEMENT FUNCTIONS

Plant operation:
● Diesel generator supply (up to 16 generators)
● Shore power supply (all gensets are inhibit to start and take on load)
Power management functions:
● Blackout handling
●Load-dependent start/stop
●Auto start mode selection
► Cyclic start
► Linear start
► Duty time start
●Auto scheduled start mode selection
► Genset power percentage
► Left power
● Priority Trip
● Heavy consumer
● Light consumer
● Reserved number of running gensets
● Safety stop, safety trip
●Safety mode (reserve an additional unit running on load)
●Limit network-connected gensets numbers
●Busbar breaking handle
4.

SPECIFICATION

Parameter
Working Voltage
Overall Consumption
AC Input:
3 Phase 4 Wire
3 Phase 3 Wire
2 Phase 3 Wire
Single Phase
Alternator Frequency
Flexible Relay Output
GOV
AVR
FREQ IN
VOLT IN
Case Dimensions
Panel Cutout
CT Secondary Current
HMC6 Power Management Controller User Manual
Table 3 – Specification Parameters
DC8. 0V to 35. 0V, continuous power supply
<4W (Standby mode: ≤2W)
AC15V - AC360V (ph-N)
AC30V - AC620V (ph-ph)
AC15V - AC360V (ph-N)
AC15V - AC360V (ph-N)
50Hz/60Hz
8A AC250V volts free output
DC(-10~10)V/(-20~20)mA
DC(-10~10)V /(-20~20)mA
DC(-10~10)V
DC(-10~10)V
266mm x 182mm x 45mm
214mm x 160mm
Rated 5A
Content
Page 8 of 87