Smartgen HMC6 User Manual page 77

Power management controller
Table of Contents

Advertisement

No.
Item
Reactive Power Control
Voltage
Control
10
Relay
Control
Load Parallel Ramp
11
Minimum
12 Fixed Active Power%
13 Fixed Reactive Power Mode
14 Fixed Reactive%
SG-DG Grid Connection
15
Time
16 Fixed Min. On-load%
17 Fixed Max. On-load%
Max. Load% of SG
18
Receiving
19 DG Stop% When SG
HMC6 Power Management Controller User Manual
Range
Gain
(0-500) %
Stability
(0-2000) %
Response
(0.1-4.00)Hz/s
Stability
(0.01-1.60)s
Gain
(0-30000)%
Dead Band
(0-10.0)%
(0-100.0)%
(0-100.0)%
(0-1)
(0-100.0)%
(0-999.9)s
(0-100.0)%
(0-100.0)%
(0-100.0)%
(0-100.0)%
Default
20
The internal analog voltage is adjusted to
control the generator voltage after parallel
20
connection.
1.20
0.20
The internal relay is adjusted to control the
generator voltage after parallel connection.
10
1.0
The active power percentage of the unit
1.0
from soft unloaded to the opening.
The percentage of active power output in
30.0
fixed power mode.
0
0: Power Percentage; 1: Power Factor
The percentage of reactive power output in
8.0
fixed power mode.
The maximum grid connection time of SG
60.0
and DG.
When the controller works in both SG mode
and fixed power mode, if the total load is
lower than the active power of fixed output
of SG, the maximum percentage value of
0.0
DG, and the remaining power is carried by
SG.
If this value is 0, when the total power is
lower than the fixed active power output of
SG, DG does not start with load.
When the controller works in both SG mode
and fixed power mode, if the total load is
greater than the fixed active power
percentage of SG and DG, DG will be
loaded to the fixed active power
100.0
percentage, the remaining power will be
loaded by SG as much as possible and the
maximum load will be the setting value. If
the total load is even greater, it will be
balanced by SG and DG.
When the controller works in both SG mode
and load-receiving mode, if SG on-load
100.0
mode is effective, the load must be lower
than receiving rated power percentage( the
setting value) before SG is closing.
50.0
When the controller works in both SG mode
Description
Page 77 of 87