Smartgen HMC6 User Manual page 25

Power management controller
Table of Contents

Advertisement

No.
Types
SG
&
DG
12
Parallel No. Out
of Limit
SG Insufficient
13
Capacity
DG Insufficient
14
Capacity
Timeout of SG
15
&
DG
Grid-connection
Switch Protection
1
Fail to Close
2
Fail to Open
Abnormal Trip
3
of Main Switch
External
of
4
Main
Switch
Open
BUS
Bar
5
Breakdown
Feedback Fault
SG
Solenoid
6
Valve Fault
Module Protection
1
Over Volt
HMC6 Power Management Controller User Manual
When the controller detects that the number of DG in
the network exceeds the limit when SG synchronizes,
SG & DG parallel number exceeds the limit and alarms.
When the controller detects that SG capacity is unable
to receive the total loads, SG capacity is insufficient to
output and an alarm is given.
When the controller detects that SG capacity is unable
to receive the total loads, DG & DG parallel number
exceeds the limit and alarms.
When the controller detects timeout of
grid-connection, it outputs and alarms.
When controller detects that there is no Close signal
after the Close delay has expired, it will initiate a trip
alarm.
When controller detects that there is no Open signal
after the Open delay has expired, it will initiate a trip
alarm.
When the controller detects that the main switch
abnormal trip input port is active, the controller
initiates an alarm signal.
When the controller is grid-connected in non-manual
mode, it detects that the feedback input port of
generation closing is inactive and the voltage, power
and current are both 0, then the controller initiates an
alarm signal.
When using BUS bar breaker, if the Bus bar breakdown
input is active of other controllers on bus tie, but the
current bus breakdown input is inactive, an alarm is
given.
When the SG mode is enabled and the input port is
configured with the shaft solenoid valve closing
feedback is effective, alarm will be given if the
feedback state of the shaft solenoid valve closing and
opening is inconsistent with that of the controller.
When controller detects the power supply voltage has
exceeded the set value, it will initiate a warning alarm.
Description
Alarm Type
Warn
It is active when it is SG
mode
Warn
It is active when it is SG
mode
Warn
It is active when it is SG
mode
SG & DG
Warn
It is always active
Lock
It is active after the switch
has closed.
Lock
It is active after the switch
has opened.
Trip
It is active after it is
closed.
Trip
It is active after it is
closed.
Warn
It is active after Bus bar
breakdown is enabled.
Warn
SG mode enables and
input port configures with
solenoid
feedback is effective.
Warn
Always active
valve
closing
Page 25 of 87