No.
Items
Voltage 3 Set
28
29
30
31
Over
32
Frequency 1
33
Set
34
35
Over
36
Frequency 2
Set
37
38
39
Over
40
Frequency 3
Set
41
42
43
Under
44
Frequency 1
Set
45
46
47
Under
48
Frequency 2
Set
49
50
51
Under
HMC6 Power Management Controller User Manual
Parameter Range
0: Disable
1: Enable
Set value
(50-100)%
Delay
(0.1-100.0)s
Alarm
(0-5)
Type
(0-1)
Action
0: Disable
1: Enable
Set value
(80-120)%
Delay
(0.1-100.0)s
Alarm
(0-5)
Type
(0-1)
Action
0: Disable
1: Enable
Set value
(80-120)%
Delay
(0.1-100.0)s
Alarm
(0-5)
Type
(0-1)
Action
0: Disable
1: Enable
Set value
(80-120)%
Delay
(0.1-100.0)s
Alarm
(0-5)
Type
(0-1)
Action
0: Disable
1: Enable
Set value
(50-100)%
Delay
(0.1-100.0)s
Alarm
(0-5)
Type
(0-1)
Action
0: Disable
1: Enable
Set value
(50-100)%
Delay
(0.1-100.0)s
Alarm
(0-5)
Type
Action
(0-1)
Default
70
1.0
2:Trip
1:Enable
105
5.0
1:Warn
1:Enable
107
3.0
2:Trip
0:Disable
Setting
110
generator rated frequency. Delay value
1.0
and return value can be set.
2:Trip
1:Enable
95
5.0
1:Warn
1:Enable
93
3.0
2:Trip
0:Disable
Description
value
is
percentage
Page 52 of 87