Smartgen HMC6 User Manual page 24

Power management controller
Table of Contents

Advertisement

No.
Types
Reverse Power
1
1
Reverse Power
2
2
3
Over Power 1
4
Over Power 2
Non
Essential
5
Load 1 Trip
Non
Essential
6
Load 2 Trip
Non
Essential
7
Load 3 Trip
Failed
to
8
Unload
Gen Capacity
9
Insufficient
Unbalanced
10
Distribution of
Active Power
Unbalanced
11
Distribution of
Reactive Power
HMC6 Power Management Controller User Manual
When controller detects the reverse power value
(power is negative) has fallen below than the set value
1, it will initiate a trip alarm.
When controller detects the reverse power value
(power is negative) has fallen below than the set value
2, it will initiate a trip alarm.
When controller detects the power value (power is
positive) has exceeded the set value 1, it will initiate a
warning alarm.
When controller detects the power value (power is
positive) has exceeded the set value 2, it will initiate a
trip alarm.
When controller detects the power value (power is
positive) has exceeded the Non Essential Load 1 Trip
set value, it will initiate a trip alarm.
When controller detects the power value (power is
positive) has exceeded the Non Essential Load 2 Trip
set value, it will initiate a trip alarm.
When controller detects the power value (power is
positive) has exceeded the Non Essential Load 3 Trip
set value, it will initiate a trip alarm.
When controller detects genset offload surpasses
unload delay, it will initiate an alarm.
When controller detects all normal gensets are
network connected and the remaining power cannot
request power, it will initiate an alarm.
When
the
controller
distribution of active power percentage is greater than
the set value, the unbalanced active power distribution
outputs and alarms.
When
the
controller
distribution of reactive power percentage is greater
than the set value, the unbalanced reactive power
distribution outputs and alarms.
Description
detects
the
unbalanced
detects
the
unbalanced
Alarm Type
Warn
It is active after the switch
has closed.
Trip
It is active after the switch
has closed.
Warn
It is active after the switch
has closed.
Trip
It is active after the switch
has closed.
Warn (Non Essential Load
1 Trip)
It is active after the Non
Essential Load switch 1
has closed.
Warn (Non Essential Load
2 Trip)
It is active after the Non
Essential Load switch 2
has closed.
Warn (Non Essential Load
3 Trip)
It is active after the Non
Essential Load switch 3
has closed.
Warn
It is active after it is
closed.
Warn
It is active always.
Warn
It
is
active
unbalanced distribution of
active power is enabled.
Warn
It
is
active
unbalanced distribution of
reactive power is enabled.
Page 24 of 87