Smartgen HMC6 User Manual page 73

Power management controller
Table of Contents

Advertisement

No.
Items
Communication
11
Alarm Action
MSC Communication
12
Speed
13
Starting Options
14
Bus Fail Start Gens
Bus Fail Gens
15
Running
Running Gensets
16
Number Reserved
17
Blackout Inhibit
Uninterrupted Power
18
Supply
19
Delay Priority Action
20
Highest Priority
HMC6 Power Management Controller User Manual
Parameter Range
Default
(0-2)
1
(0-2)
1
(0-2)
0
(0-16)
0
(0-3600)s
600
(1-16)
1
(0-1)
0
(0-1)
0
(0-1)
0
(0-1)
0
Description
Alarm action when MSC bus detects that the
modules
is
less
communication amount.
MSC communication baud rate
0:500kbps;1:250kbps;
2:125kbps.
0: Linear start; 1: Cycle start; 2: Duty time start
Number of gensets started when busbar power
dropout.
Gensets running time when busbar power
dropout.
Minimum on-load running gensets on the Busbar.
0: Disable; 1: Enable.
In auto mode, enable "Blackout Inhibit", loading
gensets on the busbar are prohibited from
opening due to factors other than over speed,
over frequency, emergency trip and stop, and
over-current, and the faulty units must be
switched off after the other normal units are
switched on.
0: Disable; 1: Enable.
In auto mode, enable "Uninterrupted Power
Supply", if loading gensets on the busbar with trip
or shutdown alarms, the faulty units must be
switched off after the other normal units are
switched on;
If voltage or frequency fault trip or shutdown,
faulty units will wait for other normal units start
and running normally to meet with loading
conditions, and then switch off the faulty units
and close the normal units.
If enabled this function, gensets status on the
busbar cannot change due to changes of the
priority. it is active only when busbar need to
calling more other gensets to start.
If enabled this function, press button by highest
priority, then current genset will become highest
priority; other genset busbar priorities make order
refresh.
If disabled this function, it will make current
genset priority become higher, but not change
than
the
set
multi-unit
Page 73 of 87

Advertisement

Table of Contents
loading

Table of Contents