(f) CC-Link IE Field Network module
The precautions for using CC-Link IE Field Network cables are described below.
• For CC-Link IE Field Network module, use CC-Link IE Field Network cables (SC-E5EW-S M,
manufactured by Mitsubishi Electric System & Service Co., Ltd.).
• A CC-Link IE Field Network cable is a shielded cable. Remove a part of the shield as shown below and
ground the largest possible exposed section to the ground.
To ground the cables for external wiring, refer to Page 388, Appendix 7.1 (3) (d)
(g) I/O signal cables and other communication cables
As for the following, ground the shield of cables (in the same way as explained in
(1) ) when it is extended out of the control panel.
• I/O signal cable (including common cable)
• RS-232 cable
(h) Extension cables
Ground the shield of cables (in the same way as explained in
extended out of the control panel.
(i) Power cables for external power supply terminal
Use a CE-marked AC-DC power supply as an external power supply for the following modules. Install the AC-
DC power supply in the control panel where the module is installed. Keep the length of the power cable
connected to the external power supply terminal to 30m or less.
• Analog-digital converter module
• Digital-analog converter module
• High-speed counter module
• Positioning module
• Temperature control module
(4) External power supply
Use a CE-marked external power supply and ground the FG terminal.
(External power supply used for the tests conducted by Mitsubishi: TDK-Lambda DLP-120-24-1, IDEC PS5R-
SF24)
(5) Power supply module
Ground the LG and FG terminals after short-circuiting them.
(6) SD memory card
The L1MEM-2GBSD and L1MEM-4GBSD are compliant with IEC61131-2 when used in the MELSEC-L series
CPU module.
CC-Link IE Field Network cable
Shield
Page 386, Appendix 7.1 (3) (a)) when it is