Error
Error Contents and Cause
Code
[CONTROL-BUS. ERR.]
An error was detected on the system bus.
■Collateral information
• Common Information: Module No. (Slot No.)
• Individual Information:-
■Diagnostic Timing
• At power-on/At reset
1416
[CONTROL-BUS. ERR.]
An error was detected on the system bus in the
multiple CPU system.
■Collateral information
• Common Information: Module No. (Slot No.)
• Individual Information:-
■Diagnostic Timing
• At power-on/At reset
[CONTROL-BUS. ERR.]
A reset signal error was detected on the system
bus.
■Collateral information
1417
• Common Information:-
• Individual Information:-
■Diagnostic Timing
• Always
[CONTROL-BUS.ERR.]
In the redundant system, the control system
cannot access the extension base unit because it
has failed to acquire an access right.
1418
■Collateral information
• Common Information:-
• Individual Information:-
■Diagnostic Timing
• At power-ON/At reset/At Switching execution
[MULTI-C.BUS ERR.]
The error of host CPU is detected in the Multiple
CPU high speed bus.
■Collateral information
1430
• Common Information:-
• Individual Information:-
■Diagnostic Timing
• At power-on/At reset
[MULTI-C.BUS ERR.]
The communication error with other CPU is
detected in the Multiple CPU high speed bus.
■Collateral information
1431
• Common Information: Module No. (CPU No.)
• Individual Information:-
■Diagnostic Timing
• At power-on/At reset
[MULTI-C.BUS ERR.]
The communication time out with other CPU is
detected in the Multiple CPU high speed bus.
■Collateral information
1432
• Common Information: Module No. (CPU No.)
• Individual Information:-
■Diagnostic Timing
• At power-on/At reset
144
Corrective Action
Reset the CPU module and run it again.
If the same error code is displayed again, the
cause is a failure of the intelligent function module,
CPU module, or base unit. (Please consult your
local Mitsubishi representative, explaining a
detailed description of the problem.)
Reset the CPU module and run it again. If the
same error code is displayed again, the cause is a
hardware failure of the CPU module, Q6 WRB, or
extension cable. (Please consult your local
Mitsubishi representative, explaining a detailed
description of the problem.)
Reset the CPU module and run it again. If the
same error code is displayed again, the cause is a
failure of the CPU module. (Please consult your
local Mitsubishi representative, explaining a
detailed description of the problem.)
• Take noise reduction measures.
• Check the main base unit mounting status of the
CPU module.
• Reset the CPU module and run it again. If the
same error code is displayed again, the cause is
a failure of the CPU module. (Please consult
your local Mitsubishi representative, explaining
a detailed description of the problem.)
Reset the CPU module and run it again. If the
same error code is displayed again, the cause is a
failure of the CPU module. (Please consult your
local Mitsubishi representative, explaining a
detailed description of the problem.)
LED Status
Corresponding
CPU Status
CPU
*8
Qn(H)
QnPH
QnU
Q00CPU
Q01CPU
QnU
QnPRH
RUN:
Off
ERR.:
*15
QnPRH
Flicker
CPU Status:
Stop
*20
QnU
*8