(b) Grounding a twisted pair cable
• Use a shielded twisted pair cable for connection to the 10BASE-T or 100BASE-TX connector. Strip a part
of the jacket of the shielded twisted pair cable as shown below and ground the exposed shield to the
ground as much as possible
(c) Grounding a Ver.1.10-compatible CC-Link dedicated cable
Ground the shield of a cable connected to the CC-Link module or any of the CC-Link stations which is the
farthest from the input power inside the control panel within 30cm from the module or station.
Ver.1.10-compatible CC-Link dedicated cable is a shielded cable. Strip a part of the jacket of the cable as
shown below and ground the exposed shield to the ground as much as possible.
Use the specified Ver.1.10-compatible CC-Link dedicated cable.
Use the FG terminals of the CC-Link module and CC-Link stations as shown below to connect to the FG line
inside the control panel.
Master module
(Blue)
DA
Terminating
(White)
resistor
DB
(Yellow)
DG
SLD
Ver.1.10-compatible
FG
CC-Link dedicated
.
Shielded twisted pair cable
Shield
Ver.1.10-compatible CC-Link
dedicated cable
Shield
Remote module
(Blue)
(Blue)
DA
(White)
(White)
DB
(Yellow)
(Yellow)
DG
SLD
FG
cable
Local module
(Blue)
DA
(White)
DB
(Yellow)
DG
SLD
Ver.1.10-compatible
CC-Link dedicated
FG
cable
APPENDICES
A
Terminating
resistor
387