Mitsubishi MELSEC L Series User Manual page 188

Hide thumbs Also See for MELSEC L Series:
Table of Contents

Advertisement

Error
Error Contents and Cause
Code
[SFC PARA. ERROR]
The parameter setting is illegal.
• The block 0 does not exist although "Autostart
Block 0" was selected in the SFC tab in the PLC
Parameter dialog box.
3200
■Collateral information
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• STOP→RUN
[SFC PARA. ERROR]
The block parameter setting is illegal.
■Collateral information
3201
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• STOP→RUN
[SFC PARA. ERROR]
The number of step relays specified in the device
setting of the PLC parameter dialog box is less
than that used in the program.
3202
■Collateral information
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• STOP→RUN
[SFC PARA. ERROR]
Other than "Scan" and "Wait" is set for "Execute
Type" in the Program tab of the PLC Parameter
dialog box.
■Collateral information
3203
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[SP. PARA ERROR]
The start I/O number in the intelligent function
module parameter set on GX Configurator differs
from the actual I/O number.
■Collateral information
3300
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN/At writing to
programmable controller
186
Corrective Action
Read the individual information of the error using
the programming tool to identify the numeric
value (parameter No.). Check the parameters
corresponding to the value, and correct them as
necessary.
*5
Check the parameter setting.
*4
LED Status
Corresponding
CPU Status
CPU
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
QnU
LCPU
Qn(H)
QnPH
QnPRH
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)
QnPH
QnPRH
QnU
LCPU
QCPU
LCPU
*8