Error
Error Contents and Cause
Code
[FILE SET ERROR]
Automatic write to standard ROM was performed
on the CPU module that is incompatible with
automatic write to standard ROM.
(Memory card where automatic write to standard
ROM was selected in the boot file was fitted and
the parameter enable drive was set to the memory
card.)
■Collateral information
• Common information: File name/Drive name
• Individual information:-
■Diagnostic Timing
• At power-on/At reset
[FILE SET ERROR]
The file specified with a parameter does not exist.
■Collateral information
• Common information: File name/Drive name
2400
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/At writing to programmable
controller/STOP→RUN
[FILE SET ERROR]
• The file specified with a parameter does not
exist.
• When using a file in an SD memory card, the SD
memory card is being disabled by SM606 (SD
memory card forced disable instruction).
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/At writing to programmable
controller/STOP→RUN
[FILE SET ERROR]
Program memory capacity was exceeded by
performing boot operation or automatic write to
standard ROM.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/At writing to programmable
controller
[FILE SET ERROR]
Program memory capacity was exceeded by
performing boot operation.
■Collateral information
2401
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/At writing to programmable
controller
[FILE SET ERROR]
The file specified by parameters cannot be made.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/At writing to programmable
controller/STOP→RUN
Corrective Action
• Execute automatic write to standard ROM on
the CPU module which is compatible with
automatic write to standard ROM.
• Write parameters and programs to the standard
ROM using the programming tool.
• Change the memory card for the one where
automatic write to standard ROM has not been
set, and perform boot operation from the
memory card.
Read the individual information of the error using
the programming tool to identify the numeric
value (parameter No.). Check the drive name and
file name of the parameter corresponding to the
value, and correct it as necessary. Create the
specified file and write it to the CPU module.
• Read the individual information of the error
using the programming tool to identify the
numeric value (parameter No.). Check the drive
name and file name of the parameter
corresponding to the value, and correct it as
necessary. Create the specified file and write it
to the CPU module.
• Cancel the SD memory card forced disable
instruction.
• Check and correct the parameters (boot
setting).
• Delete unnecessary files in the program
memory.
• Choose "Clear program memory" for boot in the
parameter so that boot is started after the
program memory is cleared.
• Read the individual information of the error
using the programming tool to identify the
numeric value (parameter No.). Check the drive
name and file name of the parameter
corresponding to the value, and correct it as
necessary.
• Format the drive.
• Delete unnecessary files on the drive to
increase free space.
APPENDICES
LED Status,
Corresponding
CPU Status
CPU
*8
Qn(H)
QnPH
QnPRH
QCPU
LCPU
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
*8
Qn(H)
QnPH
QnPRH
QnU
LCPU
QCPU
LCPU
167