Error
Error Contents and Cause
Code
[SP. UNIT LAY ERR.]
• In the I/O Assignment tab of the PLC parameter
dialog box, "Intelligent" (intelligent function
module) is set for the slot where an I/O module
is mounted, and vice versa.
• In the I/O Assignment tab of the PLC parameter
dialog box, a module other than a CPU module
or empty is set for the slot where a CPU module
is mounted, and vice versa.
• In the I/O assignment setting of the PLC
parameter, switch setting was made to the
module that has no switch setting.
• In the I/O assignment setting of the PLC
parameter dialog box, the number of points
assigned to the intelligent function module is
less than the number of points of the mounted
module.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information:-
■Diagnostic Timing
• At power-on/At reset
[SP. UNIT LAY ERR.]
• In the I/O Assignment tab of the PLC parameter
dialog box, "Intelligent" (intelligent function
module) is set for the slot where an I/O module
is mounted, and vice versa.
• In the I/O Assignment tab of the PLC parameter
dialog box, a module other than a CPU module
or empty is set for the slot where a CPU module
is mounted, and vice versa.
• In the I/O assignment setting of the PLC
parameter dialog box, the number of points
assigned to the intelligent function module is
2100
less than the number of points of the mounted
module.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information:-
■Diagnostic Timing
• At power-on/At reset
[SP. UNIT LAY ERR.]
• In the I/O Assignment tab of the PLC parameter
dialog box, "Intelligent" (intelligent function
module) or a branch module is set for the
position where an I/O module is connected.
• In the I/O Assignment tab of the PLC parameter
dialog box, "Input" (input module), "Output"
(output module), or a branch module is set for
the position where an intelligent function module
is connected.
• In the I/O Assignment tab of the PLC parameter
dialog box, "Input" (input module), "Output"
(output module), or "Intelligent" (intelligent
function module) is set for the position where a
branch module is connected.
• In the I/O Assignment tab of the PLC parameter
dialog box, switch settings are configured for the
module that does not support the setting.
• In the I/O Assignment tab of the PLC Parameter
dialog box, the number of points assigned to the
intelligent function module is less than that of the
mounted module.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information:-
■Diagnostic Timing
• At power-on/At reset
Corrective Action
• Set the I/O assignment again so that the setting
matches with the mounting status of the
intelligent function module or the CPU module.
• Delete the switch setting in the I/O assignment
setting of the PLC parameter.
Set the I/O assignment again so that the setting
matches with the mounting status of the intelligent
function module or the CPU module.
• Set the I/O assignment again so that the setting
matches with the mounting status of the
intelligent function module, CPU module, or
branch module.
• Delete the switch setting.
• Reset the CPU module and run it again. If the
same error code is displayed again, the cause
is a hardware failure of the CPU module, I/O
module, intelligent function module, END cover,
branch module, or extension module. (Please
consult your local Mitsubishi representative,
explaining a detailed description of the
problem.)
APPENDICES
LED Status,
Corresponding
CPU Status
CPU
Qn(H)
QnPH
QnPRH
QnU
RUN:
Q00J/Q00/Q01
Off
ERR.:
Flicker
CPU Status:
Stop
LCPU
151