Error
Error Contents and Cause
Code
[LINK PARA. ERROR]
• The number of modules actually mounted is
different from that is set in Network parameter
for MELSECNET/H.
• The head I/O number of actually installed
modules is different from that designated in the
network parameter of MELSECNET/H.
• Parameter-set data cannot be used.
• The network type of MELSECNET/H is
3100
overwritten during power-on. (When changing
the network type, switch RESET to RUN.)
• The mode switch of MELSECNET/H module
is outside the range.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[LINK PARA. ERROR]
The link refresh range exceeded the file register
capacity.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic Timing
• When an END instruction executed
[LINK PARA. ERROR]
• When the station number of the MELSECNET/H
module is 0, the PLC-to-PLC network parameter
has been set.
• When the station number of the MELSECNET/H
module is other than 0, the remote master
3101
parameter setting has been made.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[LINK PARA. ERROR]
The refresh parameter for the CC-Link IE module
is outside the range.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
180
Corrective Action
• Check the network parameters and actual
mounting status, and if they differ, make them
matched. If any of the network parameters is
corrected, write it to the CPU module.
• Check the set number of extension base units.
• Check the connection status of the extension
base units and extension cables.
Check the connection of the GOT if it is bus-
connected to the main base unit or extension
base unit.
If an error occurs even after taking the above
*12
measures, the cause is a hardware failure.
(Please consult your local Mitsubishi
representative, explaining a detailed description
of the problem.)
• Set the mode switch of MELSECNET/H
*12
module
within the range.
Change the file register file for the one that
enables entire range refresh.
Correct the type or station number of the
MELSECNET/H module in the network parameter
to meet the used system.
Set the refresh parameter within the range of
device setting.
LED Status
Corresponding
CPU Status
CPU
QCPU
*8
RUN:
Qn(H)
Off
QnPH
ERR.:
QnPRH
Flicker
*18
QnU
*26
LCPU
CPU Status:
Stop
*8
Qn(H)
QnPH
QnPRH
QnU
*15
Qn(H)
*17
QnPH
*17
QnPRH
QnU
*26
LCPU