Error
Error Contents and Cause
Code
[SP. PARA ERROR]
• The refresh setting of the intelligent function
module exceeded the file register capacity.
• The intelligent function module set in GX
Configurator differs from the actually mounted
module.
■Collateral information
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN/At writing to
programmable controller
[SP. PARA ERROR]
The intelligent function module's refresh parameter
setting is outside the available range.
■Collateral information
3301
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN/At writing to
programmable controller
[SP. PARA ERROR]
The setting of the refresh parameter range crosses
over the boundary between the internal user
device and the extended data register (D) or
extended link register (W).
■Collateral information
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN/At writing to
programmable controller
[SP. PARA ERROR]
The intelligent function module's refresh parameter
are abnormal.
■Collateral information
• Common information: File name
3302
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN/At writing to
programmable controller
[SP. PARA ERROR]
In a multiple CPU system, the automatic refresh
setting or other parameter setting was made to the
intelligent function module under control of another
station.
3303
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN/At writing to
programmable controller
Corrective Action
• Change the file register file for the one which
allows refresh in the whole range.
• Check the parameter setting.
• Check the auto refresh setting.
*4
• Check the parameter setting.
• Check the auto refresh setting.
*4
Set the refresh parameter range so that it does
not cross over the boundary between the internal
user device and the extended data register (D) or
extended link register (W).
*4
Check the parameter setting.
*4
• Delete the automatic refresh setting or other
parameter setting of the intelligent function
module under control of another CPU.
• Change the setting to the automatic refresh
setting or other parameter setting of the
intelligent function module under control of the
host CPU.
APPENDICES
LED Status
Corresponding
CPU Status
CPU
Q00J/Q00/Q01
*8
Qn(H)
QnPH
QnPRH
QnU
LCPU
QCPU
LCPU
RUN:
Off
ERR.:
Flicker
QnU
LCPU
CPU Status:
Stop
QCPU
LCPU
*8
Q00/Q01
*8
Qn(H)
QnPH
*18
QnU
187