Error
Error Contents and Cause
Code
[LINK PARA. ERROR]
The CC-Link link refresh range exceeded the file
register capacity.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic Timing
• When an END instruction executed
[LINK PARA. ERROR]
The network refresh parameter for CC-Link is out
of range.
■Collateral information
• Common information: File name
3106
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[LINK PARA. ERROR]
The setting of the network refresh range crosses
over the boundary between the internal user
device and the extended data register (D) or
extended link register (W).
■Collateral information
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[LINK PARA. ERROR]
• The CC-Link parameter setting is incorrect.
• The set mode is not allowed for the version of
the mounted CC-Link module.
3107
■Collateral information
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[LINK PARA. ERROR]
• When the CC-Link IE Field Network is used, the
network number set in "Network Parameter" and
"Switch Setting" is duplicated.
• No "Network Parameter" and "Switch Setting"
are configured, or the CC-Link IE Field Network
3150
module with an incorrect switch setting is
mounted.
■Collateral information
• Common information: File name
• Individual information: Parameter number
■Diagnostic Timing
• At power-on/At reset
Corrective Action
Change the file register file for the one refresh-
enabled in the whole range.
Check the parameter setting.
Set the network refresh range so that it does not
cross over the boundary between the internal
user device and the extended data register (D) or
extended link register (W).
Check the parameter setting.
• Check the parameter setting.
• Configure "Network Parameter" and "Switch
Setting", and then write network parameters
and the switch setting to the module.
APPENDICES
LED Status
Corresponding
CPU Status
CPU
*8
Qn(H)
QnPH
QnPRH
QnU
LCPU
QCPU
LCPU
QnU
RUN:
LCPU
Off
ERR.:
Flicker
CPU Status:
Stop
QCPU
LCPU
*25
QnU
*26
LCPU
185