Special
ACPU
Special
Register
Special
Register for
after
Register
Modification
Conversion
D9025
SD1025
D9026
SD1026
D9027
SD1027
D9028
SD1028
D9035
SD1035
SD648
D9036
SD1036
D9037
SD1037
Name
Meaning
Clock data
-
Clock data
(year, month)
Clock data
-
Clock data
(day, hour)
Clock data
-
Clock data
(minute,
second)
Clock data
-
Clock data
(day of week)
Extension file
Use block No.
register
×
Device number
when
Extension file
individual
registerfor
devices from
designation of
extension file
×
device number
register are
directly
accessed
Details
This register stores the last two digits of the year and the
month in BCD as shown below.
b15
to
b12 b11
to
b8 b7
to
b4 b3
to
Year
Month
This register stores the day and the hour in BCD as shown
below.
b15
to
b12b11
to
b8 b7
to
b4 b3
to
Day
Hour
This register stores the minute and the second in BCD as
shown below.
b15
to
b12b11
to
b8 b7
to
b4 b3
to
Minute
Second
This register stores the day of the week in BCD as shown
below.
b15
to
b12 b11
to
b8 b7
to
b4 b3
Always set "0"
Stores the block No. of the extension file register being used
in BCD code.
Designate the device number for the extension file register
for direct read and write in 2 words at SD1036 and SD1037
in BIN data.
Use consecutive numbers beginning with R0 of block No. 1
to designate device numbers.
16383
16384
SD1037,SD1036
Device No. (BIN data)
APPENDICES
Corre-
sponding
CPU
Example:
b0
1987, July
H8707
Example:
b0
31st, 10 a.m.
H3110
Qn(H)
QnPH
Example:
b0
35 min, 48 sec.
*1
QnU
H3548
LCPU
to
b0
Example:
Friday
H0005
Day of the week
0
Sunday
Monday
1
2
Tuesday
3
Wednesday
4
Thursday
5
Friday
6
Saturday
Extension file register
Qn(H)
0
Block No.1
to
QnPH
area
Block No.2
to
area
to
347