Error
Error Contents and Cause
Code
[SP. UNIT LAY ERR.]
• Two or more MELSECNET/H modules were
installed.
• Two or more Ethernet modules were installed.
• Three or more CC-Link modules were installed.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information:-
■Diagnostic Timing
• At power-on/At reset
2106
[SP. UNIT LAY ERR.]
• The same network number or same station
number is duplicated in the MELSECNET/H
network system.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information:-
■Diagnostic Timing
• At power-on/At reset
[SP. UNIT LAY ERR.]
The start X/Y set in the PLC parameter's I/O
assignment settings is overlapped with the one for
another module.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information:-
■Diagnostic Timing
• At power-on/At reset
2107
[SP. UNIT LAY ERR.]
The start X/Y configured in the I/O Assignment tab
of the PLC Parameter dialog box is overlapped
with that for another module.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information:-
■Diagnostic Timing
• At power-on/At reset
[SP. UNIT LAY ERR.]
• Network module A1SJ71LP21, A1SJ71BR11,
A1SJ71AP21, A1SJ71AR21, or A1SJ71AT21B
dedicated for the A2USCPU has been installed.
• Network module A1SJ71QLP21 or
A1SJ71QBR11 dedicated for the Q2ASCPU has
been installed.
• Network module AJ71LP21, AJ71LP21G,
AJ71BR11, AJ71AP21, AJ71AR21, or
2108
AJ71AT21B dedicated for the A2UCPU has
been installed.
• Network module AJ71QLP21,AJ71QLP21S,
AJ71QLP21G or AJ71QBR11 dedicated for the
Q2ACPU has been installed.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information:-
■Diagnostic Timing
• At power-on/At reset
154
Corrective Action
• Reduce the MELSECNET/H modules to one or
less.
• Reduce the Ethernet modules to one or less.
• Reduce the CC-Link modules to two or less.
• Check the network number and station number.
Make the PLC parameter's I/O assignment setting
again so it is consistent with the actual status of
the intelligent function module/special function
modules.
• Configure the start X/Y again in the I/O
Assignment tab of the PLC Parameter dialog
box according to the intelligent function module
and I/O modules connected.
• Reset the CPU module and run it again. If the
same error code is displayed again, the cause
is a hardware failure of the CPU module, I/O
module, intelligent function module, END cover,
branch module, or extension module. (Please
consult your local Mitsubishi representative,
explaining a detailed description of the
problem.)
Replace the network module for the A2USCPU,
Q2ASCPU, A2UCPU, or Q2ACPU with the
MELSECNET/H module.
LED Status,
Corresponding
CPU Status
CPU
Q00J/Q00/Q01
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
QCPU
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
LCPU
Qn(H)
*31
QnU