4-20 mA Test mode A test output of 4, 12, and 20 mA can be performed
The following settings are available.
Output item selection:
Select an item to output by 4-20 mA signal.
The measurement item set on "Display Item" P.22
can be selected as the output item.
Signal output range lower limit/signal output range
upper limit:
For the item selected in the "Output Item Select",
specify measurement value to output at lower limit
(Lo, 4 mA) and upper limit (Hi, 20 mA).
20 mA
Signal output
4 mA
Measurement
value at 4 mA
4 mA Fine adjustment:
The lower limit of signal output, 4 mA, can be fine-
tuned when there is a discrepancy between the
output value of the product and the displayed value
of a connected device such as a recorder (data
logger).
20 mA Fine adjustment:
The upper limit of signal output, 20 mA, can be fine-
tuned when there is a discrepancy between the
output value of the product and the displayed value
of a connected device such as a recorder (data
logger).
to check the signal output status to a device such as
a recorder (data logger).
Description
Measurement
value at 20 mA
Refer to
P.32
P.33,
P.34
P.35
P.36
P.37
31