7 .4 Signal outputs

The signal outputs are galvanically isolated from each other as well as from the electronic
control unit FC100-CA .

7 .4 . 1 Relay outputs R2 (DC or AC)

Connector pin assignment:
Resistive load
Max. admissible switching capacity:
Max. admissible switching current:
Max. admissible continuous current:
Max. admissible switching voltage:
Contact life at 1 A:
Inductive load - with safety circuit - AC voltage
Max. admissible switching capacity:
Max. admissible switching current:
Max. admissible continuous current:
Max. admissible switching voltage:
Contact life cos ϕ = 0.5:
Insulation voltage:
FC100-CA | Flow Meter
TECHNICAL DATA
Signal name
Limit Switch 1 / shield
Limit Switch 1 / N.O.
Limit Switch 1 / common
Limit Switch 1 / N.C.
Limit Switch 2 / shield
Limit Switch 2 / N.O.
Limit Switch 2 / common
Limit Switch 2 / N.C.
50 W
1 A
1 A
50 V
5
3 x 10
cycles
125 VA
1.25 A
1.25 A
100 V
5
2.4 x 10
cycles
signal contact - central electronic unit DC 500 V
signal contact - signal contact DC 500 V
Pin XAH
1
2
3
4
5
6
7
8
65