5 .9 . 1 Analogue output – flow velocity
This menu option allows adjustment of the flow velocity analogue output specifically to the require-
ments of the entire system.
Options are:
• OFFSET
• INITIAL VALUE
• FINAL VALUE
When entering the initial or final value, the user should observe a reasonable resolution.
With a flow volume/time unit selected in menu PHYSICAL UNITS and when setting the initial and end
values, the pertinent flow volumes will also be indicated.
5 .9 .2 Analogue output – medium temperature
In conformance with the configuration "Analogue output – flow velocity" (see chapter 5.9.1) it is possible
to adjust the medium temperature analogue output to the requirements of the entire system.
Options are:
• OFFSET
• INITIAL VALUE
• FINAL VALUE
When entering the initial or final value, the user should observe a reasonable resolution.
FC100-CA | Flow Meter
CONFIGURATION
0/4 ... 20 mA, 0/1 ... 5 V, 0/2 ... 10 V
0/20% corresponds to a flow velocity of ... [m/s] [%] [FPS]
100% corresponds to a flow velocity of ... [m/s] [%] [FPS]
0/4 ... 20 mA, 0/1 ... 5 V, 0/2 ... 10 V
0/20% corresponds to a medium temperature of ... [°C] [°F] [K]
100 % corresponds to a medium temperature of ... [°C] [°F] [K]
53