Appendix A: TV-VVTBP-E2 Points/Properties

Appendix A: TV-VVTBP-E2 Points/Properties
NOTE Engineering units shown in this document in the defaults and ranges are strictly for reference. You must
enter an integer only.

Status

Navigation:
i-Vu® / Field Assistant:
Point Name/Description
Static Pressure - Prime Variable – The current supply duct static pressure. This value is
shown on the default area graphic in i-Vu or Field Assistant.
Supply Air Temperature – If Airside Linkage Status is Active, this is the air source's
current supply air temperature. If Airside Linkage Status is Not Active, this value is from
the local SAT sensor.
Damper Position – If Control Device Type is Actuator, this is the current open damper
position.
VFD output – If Control Device Type is VFD, this is the current VFD speed capacity.
LAT Control – The status of LAT Limit duct static pressure override control of the
bypass.
LAT Airflow Increase – If LAT Control is On, this is the percent of increase in supply
airflow that the overriding LAT Duct Static Pressure Setpoint will provide above the
normal Controlling Pressure Setpoint.

Unit Configuration

Navigation:
i-Vu® / Field Assistant:
Point Name/Description
Control Device Type – The device the controller uses to control static pressure.
Power Fail Restart Delay – How long the controller delays normal operation after the
power is restored.
Automatic Deadband Adjustment – If using an actuator, set to Enable to automatically
adjust the damper for full travel to correctly scale the damper position. If using a VFD
drive, set to Disable.
TruVu™ VVTBP-E2
Installation and Start-up Guide
Properties
Control Program
>
Properties
Control Program
>
76
Status
>
Range
R:
0 to 2.0 in. H
(0 to .498 kPa)
R:
-56 to 245°F
(-48.9 to 118.3°C)
R:
0 to 100%
R:
0 to 100%
R:
On/Off
R:
0 to 100%
Unit Configuration
>
Default/Range
D:
Actuator
R:
Actuator/VFD drive
D:
60 seconds
R:
0 to 600 secs
D:
Enable
R:
Enable/Disable
O
2
©2022 Carrier.
All rights reserved.