Adjusting the TV-VVTBP-E2 driver properties
Common Alarms
On these pages, you can enable/disable, change BACnet alarm properties, or set delays for the following BACnet
alarms:
Common alarms:
•
Duplicate Address
•
Control Program
•
Controller Halted
•
Locked I/O
•
Program Stopped
•
Excessive COV
•
All Programs Stopped
Controller Generated Alarm
Description
Events
Alarm Category and Alarm
Template
Enable
Notification Class
Specific Events
On these pages, you can enable/disable, change BACnet alarm properties, or set delays for the following BACnet
alarms:
Specific alarms:
•
Flow Control Alarm
•
Reheat Valve Alarm
NOTE To set up alarm actions for controller generated alarms, see Alarms in i-Vu® Help.
Controller Generated Alarm
Description
Events
Alarm Category and Alarm
Template
Enable
Notification Class
TruVu™ VVTBP-E2
Installation and Start-up Guide
Short message shown on the i-Vu® Alarms page or in an alarm action when this
type of alarm is generated.
See Setting up an alarm source in the i-Vu® interface in i-Vu® Help.
Clear these checkboxes to disable Alarm or Return to normal messages of this
type from the TV-VVTBP-E2.
In a typical i-Vu® system, the Notification Class is 1; however, if needed, you can
associate a different notification class with the alarm. See Notification Classes
(page 46) to set up alarm delivery options for a specific Notification Class.
Short message shown on the i-Vu® Alarms page or in an alarm action when this
type of alarm is generated.
See Alarms in i-Vu® Help.
Clear these checkboxes to disable Alarm or Return to normal messages of this
type from this controller.
Do not change this field.
48
©2022 Carrier.
All rights reserved.