Wiring the DAT sensor to the TV-VVTBP-E2's inputs

Wiring the DAT sensor to the TV-VVTBP-E2's inputs
You can wire the Duct Air Temperature sensor (Part #33ZCSENDAT) to the TV-VVTBP-E2's inputs.
The TV-VVTBP-E2 must be connected to a Duct Air Temperature (DAT) sensor that monitors the temperature of the
air delivered by the air source.
NOTE This document gives instructions for wiring the sensors to the TV-VVTBP-E2. For mounting and wiring the
sensor, see the Carrier Sensors Installation Guide.
WARNING Disconnect electrical power to the TV-VVTBP-E2 before wiring it. Failure to follow this warning
could cause electrical shock, personal injury, or damage to the controller.
CAUTION
Do not run sensor or relay wires in the same conduit or raceway with Class 1 AC or DC service wiring.
Do not abrade, cut, or nick the outer jacket of the cable.
Do not pull or draw cable with a force that may harm the physical or electrical properties.
Avoid splices in any control wiring.

Wiring specifications

Cable from sensor to controller:
Maximum length:

To wire and mount the DAT sensor

Wire the sensor to the controller's IN-01 and Gnd terminal. See diagram below.
1
NOTE Sensor wiring does not have polarity. The wires can be connected to either terminal.
Using electrical tape, insulate any exposed wire to prevent shorting.
2
Connect shield to earth ground (if using shielded wire to extend cable length).
3
TruVu™ VVTBP-E2
Installation and Start-up Guide
If <100 ft (30.5 meters)
If >100 ft (30.5 meters)
500 feet (152 meters)
32
22 AWG, unshielded
22 AWG, shielded