MTBF @ 77°F (25°C)
BACnet support
Compliance

Zone sensors

You can wire ZS sensors and/or a Wireless Adapter that communicates with wireless sensors to the TV-VVTBP-E2's
Rnet port. You can have up to 10 ZS and/or wireless sensors.
NOTES
A control program can use no more than 5 ZS sensors, so you must use multiple control programs if your
Rnet network has more than 5 sensors.
ZS and wireless sensors can share the Rnet with an Equipment Touch or TruVu™ ET Display.
CAUTION Rnet power
The Rnet port provides 12 Vdc at up to 260 mA. When determining which devices to put on the Rnet, verify that
the total current draw of the sensors does not exceed the controller's Rnet power. See the sensor's Installation
and Start-up Guide to determine the power required.
TruVu™ VVTBP-E2
Installation and Start-up Guide
184,811 hours
Conforms to the BACnet Advanced Application Controller (B-AAC) and B-BBMD
Standard Device Profiles as defined in ANSI/ASHRAE Standard 135-2012 (BACnet)
Annex L, Protocol Revision 14
United States of America:
FCC CFR47, Part 15, Subpart B, Class B
Canada:
Industry Canada Compliant, ICES-003, Class B
Contains IC ID: 6713A-STM300U
Europe:
Mark, UK:
EN50491-5-2:2009; Part 5-2: EMC requirements for HBES/BACS used in
residential, commercial and light industry environment
RoHS Compliant: 2015/863/EU
REACH Compliant
7
What is the TV-VVTBP-E2?