Specifications

Driver
Maximum number of control programs*
Maximum number of BACnet objects*
Third-party BACnet integration points
NOTE Must be on the BACnet/IP network
* Depends on available memory.
Power
Actuator
Eth0, Eth1
TruVu™ VVTBP-E2
Installation and Start-up Guide
drv_fwex_< version >.driverx
2
NOTE You can run 1 VVT bypass Product Integrated
Control (PIC) and 1 programmable Zone Controller II
program, OR up to 2 Zone Controller II programs.
12000
100
24 Vac ±15%, 50–60 Hz, 50 VA
24 Vdc ±10%, 18 W
NOTE The above power consumption is for the controller only. Adding devices to
the Act Net bus increases total power consumed.
Belimo brushless DC motor, torque 45 inch-pounds (5 Nm), runtime 154 seconds
10/100 BaseT, full duplex, Ethernet ports for BACnet/IP and/or BACnet/Ethernet
communication.
Under normal operation, network traffic not destined for this controller is repeated
to the other Ethernet port. When the controller is powered off, all traffic received on
one port is mirrored to the other port.
4