Appendix B: BACnet points list

Point Name
Controlling Pressure
Setpoint
Damper Position
LAT Airflow Increase
Air Source Supply Air Temp
Maximum Duct Pressure
Setpoint
Maximum Heating SAT
Minimum Cooling SAT
Power Fail Restart Delay
Pressure Control Deadband R/W
Static Pressure - Prime
Variable
Supply Air Temperature
VFD output
Airside Linkage Status
Automatic Deadband
Adjustment
Control Device Type
LAT Control
Air Source Mode
Airside Linkage Alarm
Supply Air Temperature
Alarm
TruVu™ VVTBP-E2
Installation and Start-up Guide
Point Access
Units
R
in H2O
R
%
R
%
R
°F
R
in H2O
R/W
°F
R/W
°F
R/W
sec
in H2O
R
in H2O
R
°F
R
%
0=Not Active
R
1=Active
0=Disable
R/W
1=Enable
0=Actuator
R/W
1=VFD
0=Off
R
1=Active
1=Off
2=Warmup
3=Heat
4=Cool
R
5=Freecool
6=Pressure
7=Evac
8=Vent
0=Normal
R
1=Alarm
0=Normal
R
1=Alarm
BACnet
Default
BACnet Point Name
Value
sys_press_stpt
dpr_pos
lat_airflow_inc
link_sat
max_press_stpt
120
sat_ht_max
45
sat_cl_min
60
start_delay
0.05
press_hysteresis
static_press
sa_temp
vfd_output
a_link_status
Active (1)
auto_adjust
Inactive (0)
ctrl_type
lat_control
link_ahu_mode
air_linkage_fail
sat_alarm
81
Appendix B: BACnet points list
BACnet Object
ID
AV:1015
AV:1013
AV:5002
AV:2608
AV:5003
AV:83004
AV:83003
AV:9007
AV:3016
AV:1016
AV:1008
AV:1014
BV:2601
BV:99003
BV:99002
BV:1013
MSV:2005
BV:7030
BV:7004