To adjust input and output properties

Output values

Output
Analog (BAO)
0-10 Vdc
2-10 Vdc
12 Vdc PWM
Binary (BBO)
Relay
1
The Analog Output microblock uses the Min and Max values to linearly translate its incoming value into a
physical output signal (Volts) sent from the TV-VVTBP-E2 to a device. For example, set Min to 0 and Max to 100
for an Analog Output microblock that receives a 0 to 100% open signal from a PID microblock and that controls
a 0–10 Vdc actuator so that when the PID signal is 100%, the TV-VVTBP-E2 output is 10 Vdc. Similarly, when
the PID signal is 50%, the TV-VVTBP-E2 output is 5 Vdc.

Resolution values

Resolution is not particular to a type of input or output, but the driver handles analog and binary inputs and
outputs differently. To set these values appropriately, you should understand how the driver uses them.
Resolution
Analog Input (BAI)
Analog Output
(BAO)
TruVu™ VVTBP-E2
Installation and Start-up Guide
I/O Type
Sensor/Actuator Type
Electrical
Linear Full Range
0–10 Volt
No Translation
Electrical
Linear w/Offset,
0–10 Volt
2–10 Volts
PWM 80 Hz
No Translation
Relay/Triac
N/A
Output
Notes
The driver rounds the microblock's present value according to the resolution.
EXAMPLE If the calculated present value is 13.789 and you set the Resolution to 0.1, the
control program uses 13.8 for any calculations downstream from the microblock.
The driver rounds the wire input value to the microblock before performing any scaling
calculations.
EXAMPLE If the wire input value is 13.789 and you set the Resolution to 0.1, the
microblock uses 13.8 for any scaling calculations.
Min/Max
Engineering values associated with 0
Vdc (Min) and 10 Vdc (Max)
N/A. The Analog Output microblock will
output the same value that comes in to
the microblock.
Engineering values associated with 2
Vdc (Min) and 10 Vdc (Max)
0% (Min) and 100% (Max). The Analog
Output microblock varies the width of
the pulse based on the value that the
microblock receives.
N/A
30
1
1