Specifications

Driver
Power
Access port J12
Rnet port J13
Network Comm port J19
Comm Option port
Inputs
Binary outputs
Analog outputs
Output resolution
Real-time clock
Battery
RTU Open v3
Installation and Start-up Guide
drv_rtuopn_std
24 Vac ±10%, 50–60 Hz
20 VA power consumption
26 Vdc (25 V min, 30 V max)
Single Class 2 source only, 100 VA or less
For system start-up and troubleshooting using Field Assistant
Supports up to 5 wireless and/or ZS sensors, and one Equipment Touch or
TruVu™ ET Display
Supplies 12 Vdc/210 mA power to the Rnet across its rated temperature
range.
NOTE Ambient temperature and power source fluctuations exceeding the
listed operating ranges may reduce the power supplied by the Rnet port.
NOTE If the total power required by the sensors on the Rnet exceeds the power
supplied by the Rnet port, use an external power source. The Wireless Adapter,
Equipment Touch, or TruVu™ ET Display must be powered by an external power
source. See the specifications in each device's Installation and Start-up Guide to
determine the power required.
For communication with the controller network using BACnet ARC156 (156 kbps)
or BACnet MS/TP (9600 bps – 76.8 kbps)
For communication with the LonWorks Option Card.
12 inputs:
Inputs 1 - 2:
4-20 mA only
Inputs 3, 5, 8, 9:
Binary, 24 Vac
Inputs 6 - 7:
Thermistor
Inputs 10 - 11:
Thermistor
Rnet sensor
8 relay outputs, contacts rated at 3 A max @ 24 Vac. Configured normally open.
AO-1: 2-10 Vdc or 4-20 mA (configurable on jumper J3)
AO-2: 0-10 Vdc or 2-10 Vdc SC-VFD input
10 bit D/A
Battery-backed real-time clock keeps track of time in event of power failure
10-year Lithium CR2032 battery retains the following data for a maximum of
10,000 hours during power outages: control programs, editable properties,
schedules, and trends.